Installation
Introduction
Environmental Characteristics
Electromagnetic Compatibility Standard Level / Class Value
Emission Tests
Disturbing field emission IEC 60255-25
EN 55022 A
Conducted disturbance emission IEC 60255-25
EN 55022 A
Immunity Tests – Radiated Disturbances
Immunity to radiated fields ANSI C37.90.2 (1995) 35 V/m; 25 MHz - 1 GHz
IEC 60255-22-3 10 V/m; 80 MHz - 1 GHz
IEC 61000-4-3 III 10 V/m; 80 MHz - 2 GHz
Electrostatic discharge ANSI C37.90.3 8 kV air; 4 kV contact
IEC 60255-22-2 8 kV air; 6kV contact
Immunity to magnetic fields at network frequency IEC 61000-4-8 4 30 A/m (continuous) - 300 A/m (1 - 3 s)
Immunity Tests – Conducted Disturbances
Immunity to conducted RF disturbances IEC 60255-22-6 III 10 V
Fast transient bursts ANSI C37.90.1 4 kV; 2.5 kHz
IEC 60255-22-7 A and B 4 kV; 2.5 kHz / 2 kV; 5 kHz
IEC 61000-4-4 IV 4 kV; 2,5 kHz
1 MHz damped oscillating wave ANSI C37.90.1 2.5 kV; 2.5 kHz
IEC 60255-22-1 2.5 kV CM; 1 kV DM
Surges IEC 61000-4-5 III 2 kV CM; 1 kV DM
Voltage interruptions IEC 60255-11 100 % during 100 ms
Hardware Parameters Standard Level / Class Value
In Operation
Vibrations IEC 60255-21-1 2 1 Gn; 10 Hz - 150 Hz
IEC 60068-2-6 Fc 2 Hz - 13.2 Hz ; a = ±1 mm
Shocks IEC 60255-21-2 2 10 Gn / 11 ms
Earthquakes IEC 60255-21-3 2 2 Gn (horizontal axes)
1 Gn (vertical axes)
De-Energized
Vibrations IEC 60255-21-1 2 2 Gn; 10 Hz - 150 Hz
Shocks IEC 60255-21-2 2 27 Gn / 11 ms
Jolts IEC 60255-21-2 2 20 Gn / 16 ms
Climate Variables Standard Level / Class Value
In Operation
Exposure to cold IEC 60068-2-1 Ad –25°C (–13°F)
Exposure to dry heat IEC 60068-2-2 Bd +70°C (+158°F)
Continuous exposure to damp heat IEC 60068-2-78 Cab 10 days; 93 % RH; 40°C (104°F)
Salt mist IEC 60068-2-52 Kb/2 6 days
Influence of corrosion/2-gas test IEC 60068-2-60 21 days; 75 % RH; 25°C (77°F);
0.5 ppm H
2
S; 1 ppm SO
2
Influence of corrosion/4-gas test IEC 60068-2-60 21 days; 75 % RH; 25°C (77°F);
0.01 ppm H
2
S; 0.2 ppm SO
2
;
0.2 ppm NO
2
; 0.01 ppm CI
2
In Storage
(1)
Temperature variation with specified variation rate IEC 60068-2-14 Nb –25°C to +70°C (–13°F to +158°F); 5°C/min
Exposure to cold IEC 60068-2-1 Ab –25°C (–13°F)
Exposure to dry heat IEC 60068-2-2 Bb +70°C (+158°F)
Continuous exposure to damp heat IEC 60068-2-78 Cab 56 days; 93 % RH; 40°C (104°F)
IEC 60068-2-30 Db 6 days; 95 % RH; 55°C (131°F)
Safety Standard Level / Class Value
Enclosure Safety Tests
Front panel tightness IEC 60529 IP52 Other panels IP20
NEMA Type 12
Fire withstand IEC 60695-2-11 650°C (1200°F) with glow wire
Electrical Safety Tests
1.2/50 µs impulse wave IEC 60255-5 5 kV
(2)
Power frequency dielectric withstand ANSI C37.90 1 kV 1 min (indication output)
1.5 kV 1 min (control output)
IEC 60255-5 2 kV 1 min
(3)
Certification
European
Directives:
e EN 50263 harmonized standard 89/336/EEC Electromagnetic Compatibility (EMC) Directive
b 92/31/EEC Amendment
b 93/68/EEC Amendment
73/23/EEC Low Voltage Directive
b 93/68/EEC Amendment
UL UL508 - CSA C22.2 no. 14-95 File E212533
CSA CSA C22.2 no. 14-95 / no. 94-M91 / no. 0.17-00 File 210625
(1) Sepam™ must be stored in its original packing.
(2) Except for communication: 3 kV in common mode and 1 kV in differential mode.
(3) Except for communication: 1 kVrms.