1
© 2007 Schneider Electric. All Rights Reserved.
63230-216-229-B1
Installation
ACE969TP and ACE969FO
Multi-Protocol Interfaces
PE50470
Function
The ACE969 multi-protocol communication interfaces function with Sepam™ Series
20, 40, or 80. They have two communication ports to connect a Sepam™ to two
independent communication networks:
b The S-LAN (Supervisory Local Area Network) port to connect Sepam™ to a
supervision network using one of the three following protocols:
v IEC 60870-5-103
v DNP3
v RTU Modbus
The communication protocol is selected when setting Sepam™ parameters
b The E-LAN (engineering local area network) port, reserved for Sepam™
remote parameter setting and operation using the SFT2841 software
There are two versions of the ACE969 interfaces. Each has different S-LAN ports:
b ACE969TP (Twisted Pair) is for connecting to an S-LAN network using a two-
wire RS485 connection
b ACE969FO (Fiber Optic) is for connecting to an S-LAN network using a fiber-
optic connection (star or ring)
The E-LAN port is always a two-wire RS485 connection.
ACE969TP Communication Interface
PE50471
ACE969FO Communication Interface