40
© 2007 Schneider Electric. All Rights Reserved.
1
63230-216-229-B1
Installation
ACE990 Core Balance CT Interface
Function
PE50037
The ACE990 adapts measurements between an MV zero sequence CT with a ratio
of 1/n (50 ≤ n ≤ 1500), and the Sepam™ residual current input.
Characteristics
Weight 0.64 kg (1.41 lb)
Assembly Mounted on symmetrical DIN rail
Amplitude accuracy ±1%
Phase accuracy < 2°
Maximum permissible current 20 kA - 1 s
(on the primary winding of an MV zero
sequence CT with a ratio of 1/50 that does not
saturate)
ACE990 zero sequence CT interface Operating temperature –5°C to +55°C (+23°F to +131°F)
Storage temperature –25°C to +70°C (–13°F to +158°F)
Description and Dimensions
ACE990 input terminal block, for connection of the zero sequence CT.
ACE990 output terminal block, for connection of the Sepam™ residual current.
DE80040
(20)
0.79
(77)
3.03
(72)
2.83
(25)
0.98
(11)
0.43
(46)
1.81
(99)
3.90
(50)
1.97
in.
(mm)
(11)
0.43
Comentários a estes Manuais