Installation
MET1482
Temperature Sensor Module
Function
PE50021
The MET1482 module can connect eight temperature sensors (RTDs) of the same
type:
b Pt100, Ni100, or Ni120 type RTDs, according to parameter setting
b Three-wire temperature sensors
b Two modules for each Sepam™ Series 80 base unit, connected by CCA770
(2 ft or 0.6 m), CCA772 (6.6 ft or 2 m), or CCA774 (13.1 ft or 4 m) cables
The temperature measurement (for example, in a transformer or motor winding)
provides for:
b thermal overload (to take ambient temperature into account)
b temperature monitoring
Characteristics
MET1482 Module
Weight 0.441 lb (0.2 kg)
Assembly On symmetrical DIN rail
Operating temperature –13°F to +158°F (–25°C to +70°C)
Environmental characteristics Same characteristics as Sepam™ base units
Temperature Sensors Pt100 Ni100/Ni120
Isolation from ground None None
Current injected in RTD 4 mA 4 mA
DE80031
Description and Dimensions
Terminal block for RTDs 1 to 4
Terminal block for RTDs 5 to 8
RJ45 connector to connect the module to the base unit with a CCA77x cord
RJ45 connector to link up the next remote module with a CCA77x cord
(according to application)
Grounding terminal
1 The jumper for impedance matching with load resistor (Rc) is set to:
b , if the module is not the last interlinked module (default position)
b Rc, if the module is the last interlinked module
2 The jumper used to select module number is set to:
b MET1: first MET1482 module, to measure temperatures T1 to T8
(default position)
b MET2: second MET1482 module, to measure temperatures T9 to T16
(for Sepam™ Series 40 and Series 80 only)
(1) 70 mm (2.8 in) with CCA77x cord connected
3.46
(88)
5.67
(144)
(30)
(1)
1.18
in.
(mm)