Section 5.4 Fault Finding and User Repair
3BUR 001 085R0001 REV A 5-3
communication with the smart device. The third message is generated when an error is detected
for a specific smart device when data is being downloaded to the transmitter from the Smart
Device Tuning Overview Display. To view the message, use the ALL TEXT option of the
Diagnostic Package.
All three messages above have 4 digits reserved for identifying the smart device that failed,
resumed communication, or generated an error. The first 2 digits identify the network address
(1-31) of the SHIM to which the smart device is connected. The last 2 digits identify the
transmitter address (1-8) where the smart device is connected to the SHIM. Note that the smart
device’s transmitter address is preceded by a 0 (zero), and SHIM network addresses 1 through 9
are preceded by a blank space. The first and third message above also contain a second number.
In the first message the second number has 2 digits reserved for identifying the serial I/O port to
which the SHIM is connected. This allows you to easily locate the smart device in the field and
correct the problem. The second number in the third message is 3 digit value you must decipher
to determine the problem with the smart device. The value indicates a device-specific error
code, resulting from a download error generated when data is being downloaded to the
transmitter from the Smart Device Tuning Overview Display. Consult the documentation
provided by the smart device’s manufacturer for details on the code’s meaning.
All of the following messages indicate field device status problems:
SMART DEV 201 NON-PV OUT OF SENSOR LIMITS
SMART DEV 201 NON-PV BACK IN VALID RANGE
SMART DEV 201 PV OUT OF SENSOR LIMITS
SMART DEV 201 PV BACK IN VALID RANGE
SMART DEV 201 PV ANALOG OUTPUT FIXED MODE
SMART DEV 201 PV ANALOG OUTPUT NORMAL MODE
SMART DEV 201 PV ANALOG OUTPUT SATURATED
SMART DEV 201 PV ANALOG OUTPUT NON-SATURATED
The numbers in the above messages identify the smart device in the field in the same manner as
described above.
Process alarms, bad data quality, and so on is handled directly by CCF based on the input from
the input tables accessed by CCF.
Runtime tuning changes to the smart transmitter data base made by the operator at the Advant
OCS console are logged by the Event Logging Package. Tuning changes made with a hand-held
monitor are not logged.
5.4 Fault Finding and User Repair
Please refer to the Advant Controller 410 User’s Guide and the Advant Controller 460 User’s
Guide for details on trouble shooting and repair.