Smart Device (HART
®
) Interface User’s Guide
Section 3.3.5 Configuration of Smart Device (PLC) Parameters
3BUR 001 085R0001 REV A 3-27
SMART TAG
Name for the smart device of up to eight alphanumeric characters as specified during its initial
configuration.
NOTE
The SMART TAG value must be unique system wide.
SMART ADDRESS
Channel on the SHIM where the smart device is connected. You can connect up to four smart
devices to a SHIM-4, therefore, valid transmitter addresses for devices connected to a SHIM-4
are 1 through 4. You can connect up to eight smart devices to a SHIM-8, therefore, valid
transmitter addresses for devices connected to a SHIM-8 are 1 through 8.
NOTE
The entry for the SMART ADDRESS is not the polling address configured
within the transmitter. It is the physical channel where the transmitter is wired to
the SHIM.
CHANNEL
This is the starting CCF channel number that the smart device’s data relates to. CCF channel
number in the range of 1 to 32767 where the first of the smart device’s four (4) input values
(primary value, secondary value, tertiary value and fourth value) should be placed.
An Advant Controller may contains multiple types of I/O in which case the different I/O use
different tables. For example, one analog input FCM can access information from an analog I/O
input channel 1 without interfering with an FCM in another loop that accesses smart device
analog channel 1.
Field range is from 1 to 32767.
Default = 0
NOTE
There is only one analog smart device table in a subsystem to support smart
devices. For example, if a smart device uses channel 33 for an input, channel 33
cannot be used by any other smart device as input.
DESCRIPTION
General descriptor for the smart device of up to 24 alphanumeric characters.
You must complete a line of entries in the window for each smart device connected to the
SHIM. For example, if six smart devices are connected to the SHIM, complete six lines in the
edit window.