Advant
®
Smart Device (HART
®
) Interface User’s Guide
Section 3.4.4 FCM Input Templet
3BUR 001 085R0001 REV A 3-33
Analog Input FCM Templet Planning
This description, which supplements general information on parameters of the analog input
FCM contained in the Configurable Control Functions (CCF) instruction book, includes
considerations for processing of the input variable from a smart device in the FCM, and
conditioning of the variable in the smart device. Figure 3-14 is an example of an Analog Input
Templet.
The term counts is used to label the value at the analog channel table in the smart device
interface of the Advant OCS System. The counts value is always in 16-bit integer format.
From the channel you specify in the CHANNEL NUMBER field of the templet, the current
value (counts) is accessed and converted by CCF to a result in engineering units. This is done
with a proportion defined by using your entries in the COUNTS—LOWER BOUND,
COUNTS—UPPER BOUND, ENGU—LOWER BOUND, and ENGU—UPPER BOUND
fields. The equation used is:
where:
Figure 3-14. Analog Input Templet
EU is the result of the FCM in engineering units
C is the counts from the specified channel
EU
CLC
()
HU LU
()
HC
(
LC
)
-------------------------------------------------- LU+=