Section 3.4.3 Loop Definition and FCM Templets
3BUR 001 085R0001 REV A 3-31
Edit Window on Templet—The bottom of the first page of the Loop Definition Templet has an
edit window where you list the names and types of child templets that are to be generated for
this smart device support loop.
Make entries to the FCM list for FCMs of this loop. Typically, the loop needs FCMs that input
smart device data from, and output processed data to, CCF channels in the smart device
interface.
PROCESSING RATE Enter 0 (zero) for processing on demand, or enter a rate.
The smart device input to the loop is analog, a processing
rate must be specified. NOTE:
The rate at which the SHIM scans smart device data is
three times per second. If you place a hand-held monitor
on-line with the smart device, the rate at which the SHIM
scans smart device data drops to one time per second.
The loop processing rate should not be faster than the
SHIM scan rate.
PROCESSING PHASE Leave at default value if processing rate of zero is specified.
TREND RATE Leave at 0 (default) for no trending; or enter a number: 6,
12, 60, 120, 360, 720, 1440, or 2880.
An entry must be made to this field if the measured variable
is to be trended. The entry should be chosen to best suit the
smart device variable that is specified as the measured
variable of the loop in the NAME OF MEASURED FCM
field.
ORDER OF
PROCESSING
Leave at default value. This field is not applicable to this
type of loop.
LO ENG UNIT LIMIT Specify the lower boundary for trend graphs.
(Value becomes default for LO LIMIT and LO LO LIMIT
fields on page 2 of templet.)
HI ENG UNIT LIMIT Specify the upper boundary for trend graphs.
(Value becomes default for HI LIMIT and HI HI LIMIT fields
on page 2 of templet.)
MEASUREMENT
UNITS
Enter a string of up to 6 characters such as PSIG.
The character string that you enter is used as a label
whenever the measured variable of this loop is displayed on
the operational displays. The entry for this field should be
chosen to best suit the smart device variable that is
specified as the measured variable of the loop in the NAME
OF MEASURED FCM field.
LOOP STATE Enter the word ON.
ON should be the entry for this field.