
Advant
®
Smart Device (HART
®
) Interface User’s Guide
Section 3.3.5 Configuration of Smart Device (PLC) Parameters
3BUR 001 085R0001 REV A 3-19
BASE SCAN RATE
Enter the base scan rate of the PLC scanner (in seconds). This is the rate at which the scanner
function processes requests. It is the fastest that any command can be processed.
The range for this entry is 0.2 (200 ms) to 600.0 seconds.
Default = 1 second.
Enter 1 for SHIMs.
GOOD DATA WAIT
Enter the maximum time to wait at start-up for a full set of commands to complete. When this
time has expired, CCF is allowed to continue processing.
Range for this entry is 5 to 60 seconds.
Default = 15.
Enter 60 for SHIMs.
MAX READ WAIT
Enter the maximum base rate periods to wait before forcing a set of reads. This is needed
because data writes have precedent over reads.
Range for this entry is 5 to 60 scans.
Default = 15.
EXAMPLE: (MAX READ WAIT) x (BASE SCAN RATE) = Total Read Wait Time in
seconds
15 x 10 = 150 seconds
Enter 15 for SHIMs.
Comentários a estes Manuais