Section 2.3.1 Connecting to a SHIM
3BUR 001 085R0001 REV A 2-23
devices multiplied by 5,000 pF. For smart devices without CN values, use 1.
Masters (primary and secondary) need not be counted in deriving C
f
.
2.3.1.6 Digital Signals Only
Digital signals of smart devices are brought into a Advant Controller via SHIMs connected to
the MVI serial ports.
For digital communication only with smart transmitters, a SHIM can supply loop power to
smart transmitter loops and provide digital communication to MVI port using RS-232 directly
or for multiple SHIMs using the RS-485 bus through a RS-232/485 converter.
Since analog input termination panels are not used for digital only communication with smart
devices connected to a SHIM, a 250 ohm 1% 5W resistor is required. This resistor is needed to
provide the 250 ohm HART loop resistance that converts the HART FSK current to a voltage
(1V to 5V) that the SHIM can read.
NOTE
In the field, you can tune a smart device communicating only digital signals to the
Advant Controller by attaching a hand-held monitor to its smart transmitter loop
using grapper hooks across its terminals or the resistor attached between its
corresponding SHIM Signal+ and Signal- connections. Any tuning changes you
make to the smart device with the hand-held monitor are not logged by the
Advant OCS.
2.3.1.7 Analog and Digital Signals
Advant Controllers can support both analog and digital communication with smart devices or
just digital communication as described above. The analog signal from a smart device is brought
into the Advant Controller using either S100 I/O, S800 I/O or Taylor Remote I/O (TRIO). The
digital signal from up to eight smart devices is AC coupled to the SHIM.
S100 I/O
Analog signals brought into an Advant Controller employing S100 I/O use either DSAI 130
Analog Input boards, DSAI 133 Analog Input boards or DSAX 110 Analog Input/Output
Boards. The DSAI 130 has terminations for 16 analog inputs, the DSAI 133 has terminations
for 32 analog inputs and the DSAX 110 has terminations for 8 analog inputs.
In the AC 410 the S100 I/O boards are installed in its subrack. Up to 15 boards can be installed
in the AC 410 subrack. For the AC 460 the information from S100 I/O boards come from
separate S100 I/O subracks. Up to 5 subracks can be connected to each CI540 S100 submodule
installed in the AC 460. Please refer to the S100 I/O User’s Guide, Advant Controller 410
User’s Guide, and the Advant Controller 460 User’s Guide for more information on S100 I/O
connections.
Figure 2-17 shows an example of the connections for the AI board, DSAI 130, with 4-20mA
inputs. The connection unit DSTA 131, used together with the DSAI 130 board, is provided
with screw terminals to connect 16 analog input signals.