Section 3.3.5 Configuration of Smart Device (PLC) Parameters
3BUR 001 085R0001 REV A 3-21
PROTOCOL
Enter the protocol type depending on the MVI submodule installed and protocol required.
The possible entries are:
GENERIC for CI532V05 MVI
TERMCHAR for CI532V05 MVI
ALLENBRADLEY for CI532V04 MVI
MODBUSB for CI532V02 MVI <- used for SHIMs
NOTE
Each type of MVI submodule has a special PROM set to run the various
protocols. The protocol configured above must be set to match the submodule’s
characteristics.
PORT NAME
Enter the Templet Name for the MVI_PORT object that this PLC_PORT will be connected to.
Refer to Figure 3-7 for an example of the templet name of an MVI_PORT.
NOTE
Do not configure multiple PLC_PORT objects associated with the same
MVI_PORT name.
BACKUP PORT NAME
Enter the Templet Name for the MVI_PORT object that is the back-up port for redundant
communications that this PLC_PORT will be connected to. If this field is left blank, then there
is no back-up port defined. Refer to Figure 3-7 for an example of the templet name of an
MVI_PORT.
Leave blank for SHIMs.
INTERFACE ADDR
This is used for data highways, and is the address of the interface between the serial port and the
data highway. Smart devices do not have interface address modules defined, so this value should
be left at the default value (1).
Default = 1.
Enter 1 for SHIMs.
BACKUP INT ADDR
This is the back-up interface board address of the smart device that is used to communicate with
the system. Some smart devices do not need back-up interface address modules defined, so this
value should be zero(0).
Default = 0.
Leave blank for SHIMs.