3BUR 001 085R0001 REV A 3-1
Chapter 3 Configuration
3.1 Design Considerations
This chapter describes the AdvaBuild structure builder templets required to support the Advant
Smart Device (HART) Interface. General information for using the structure builder is provided
in the AdvaBuild Basic Functions User’s Guide.
3.1.1 Advant Smart Device Interface Configuration Procedures
The basic steps required for configuring a Smart Device (HART) Interface are:
1. Plan the Smart Device Interface configuration carefully, referring to the smart device
manufacturer’s instructions as well as to this document and the related documents it
references.
2. Configure the smart devices that are to exchange analog and digital information with the
Advant Smart Device (HART) Interface.
NOTE
Initial configuration of smart devices must be done prior to installing them in the
field. This is achieved using an external device such as a PC-based configuration
package (not supplied with the interface) or a hand-held monitor.
During initial configuration, you must specify the unique tag name and
transmitter polling address for each smart device connected to a SHIM. The tag
name is used when establishing initial communication with a smart device to
obtain its unique identifier. The transmitter polling address you specify for each
smart device should be 0 (zero), allowing for the communication of both analog
and digital signals by the smart device. If you specify an address other than 0, the
analog signal is not generated with the digital signal.
3. Use the structure builder to complete the configuration of the system. The configuration of
the smart device part of the data base is described in Section 3.3, Configuration Building.
Remember to include the CCF loops that interact with the smart devices.
3.2 Capacity and Performance
The Advant OCS system can do 10 read/write commands or 250 words (2 byte words) per
second to a ModbusB device.
3.3 Configuration Building
Smart devices are connected to the Advant OCS System via an Advant Controller 460 and/or an
Advant Controller 410.