Advant
®
Smart Device (HART
®
) Interface User’s Guide
Section 3.3.4 MVI Module and Port Planning
3BUR 001 085R0001 REV A 3-15
PARITY
Use the List function key (<F4>) to list the possible values for the PARITY data required by the
serial I/O device. Use the Up Arrow or Down Arrow keys to highlight the value wanted, then
press the Accept function key (<F8>) to enter the value in the field.
The initial default value is NONE.
The possible values are:
NONE <- used for SHIMs
ODD
EVEN
SPACE
MARK
STOP BITS
Use the List function key (<F4>) to list the possible values for the number of STOP BITS
required by the serial I/O device. Use the Up Arrow or Down Arrow keys to highlight the value
wanted, then press the Accept function key (<F8>) to enter the value in the field.
The initial default value is 1.
The possible values are:
.5
1 <- used for SHIMs
1.5
2
INPUT TIMEOUT
Enter the INPUT TIMEOUT value in milliseconds or seconds (see note) that the MVI will wait
for the completion of an input operation before an error code is generated.
The initial default value is 0.
The possible values are:
0 to 999
Enter 500 for SHIMs.
NOTE
Units are in milliseconds for ModbusB.
OUTPUT TIMEOUT
Enter the OUTPUT TIMEOUT value in milliseconds or seconds (see note) that the MVI will
wait for the completion of an output operation before an error code is generated.
The initial default value is 0.
The possible values are:
0 to 999
Enter 6 for SHIMs.
NOTE
Units are in milliseconds for ModbusB.